¡@GCT-630 Ground Continuity Tester

¡@
|
¡@
|
SPECIFICATIONS |
|
| Test Current | AC 3A ~ 32A |
| ¡@ | |
| Test Voltage | MAX 8V AC Typically |
| ¡@ | |
| Measuring Resistance Range | 0 to 0.12£[, 0 to 0.6£[ 2 ranges |
| ¡@ | |
| Measuring Accuracy | 3A ~ 5A, +10% of full scale |
| 5A ~ 32A, +5% of full scale | |
| ¡@ | |
| Current Meter | Indicate the testing Current and Setting value of Warning |
| ¡@ | |
| Resistance Meter | Indicate the testing Resistance and Setting value of Fail and SUBTRACTION |
| ¡@ | |
| Switching | Zero-start operating switch |
| ¡@ | |
| Timer | 1S, 10S, 1MIN, 10MIN 4 ranges |
| ¡@ | |
| Warning |
Monitor the variation test current, when the test current is beyond+10% of the setting value, the warning operation will proceed. |
| The setting value from 3A ~ 32A | |
| ¡@ | |
| Subtraction | The resistance of testing line can be subtracted from the test value |
| The subtraction range from 0 ~ 0.1£[ | |
| Accuracy is ¡Ó10% | |
| ¡@ | |
| GO-NOGO Set |
If the test reading value is beyond the setting value, the fail will be acting, otherwise the pass will proceed. |
| The setting value from 5% ~ 100% of the test range | |
| Accuracy is ¡Ó15% of full scale (3A ~ 5A)¡F¡Ó10% of full scale (5A ~ 32A) | |
| ¡@ | |
| Remote Control |
Input high voltage range from 11V ~ 15V, low voltage range from 0 ~ 4V and input low current range below 20mA |
| ¡@ | |
| Test Mode | Normal¡Gif the warning acted then the test will stop |
| Continue¡Gif the warning acted then the test will be continuously | |
| ¡@ | |
| Buzzer | A Buzzer is sounded when the test fail acted |
| ¡@ | |
| Test Frequency | 50Hz or 60Hz independent by Line Voltage |
| ¡@ | |
| Output Signal | TEST, GO, NG, WARNING, READY, MONITOR |
| ¡@ | |
| Power Source | AC 100V/120V/220V/240V¡Ó10%, 50/60Hz |
| ¡@ | |
| Accessories | Test Lead GHT-115 x 1, Instruction manual x 1, Power cord x 1 |
| ¡@ | |
| Dimensions & Weight | 430(W) x 178(H) x 510(D) mm, Approx. 21kg |